Dual Power Distribution Box
The ATS Dual Power Distribution Box mainly consists of circuit breakers, load isolation switches, dual power automatic transfer switches, communication connectors, and other electrical components for indoor use. It uses a steel plate welding structure for the cabinet body, with the external parts made from 1.5mm thick cold-rolled steel, forming a sealed enclosure. It is characterized by being lightweight, robust, and highly durable.
Product introduction
The ATS Dual Power Distribution Box mainly consists of circuit breakers, load isolation switches, dual power automatic transfer switches, communication connectors, and other electrical components for indoor use. It uses a steel plate welding structure for the cabinet body, with the external parts made from 1.5mm thick cold-rolled steel, forming a sealed enclosure. It is characterized by being lightweight, robust, and highly durable.
Structure Characteristics
The main components include: dual power sources, circuit breakers, connectors, and the left and right side panels, along with the frame and rear cover. The ATS cabinet is designed with a sealed enclosure for indoor use, featuring a robust, lightweight structure. The cabinet doors, side panels, and top cover are all designed to be silent and aesthetically pleasing.
Operation mode: Manual
Installation method: Wall-mounted, hung type, embedded installation
Connection method: Fixed connection
External dimensions: 1600 x 700 x 500 mm
Protective earthing measures:
The cabinet's internal structure and its protective grounding parts are arranged with independent PE grounding lines that are connected directly to the cabinet's main body. It also provides clear connection points for grounding and the associated external metal parts. The frame uses cold-rolled steel plate with anti-corrosion treatment (surface phosphating and epoxy powder coating). The cabinet has a protection degree of IP30.
Waterproofing:
All metal components have anti-corrosion protection with smooth surfaces and a nice finish.
Horizontal busbar distance:
The distance between the horizontal busbar and the ground is 330 mm.
Technical parameter
|
Rated working voltage |
AC 380V (50Hz) |
|
Rated insulation voltage |
400V |
|
Overcurrent categories |
III |
|
Material |
IIIa |
|
Pollution degree |
Class III |
|
Electric clearance |
≥5.5mm |
|
Clearance between screws |
≥6.3mm |
|
Main (horizontal busbar) rated voltage, short-circuit withstand current, and rated short-time withstand current |
400A, 6kA/1s, 10.2kA for the main switch |
|
Distribution (control) cabinet loop quantity |
4 circuits |
|
Distribution (control) cabinet circuit rated current |
100A × 4 |
|
Distribution (control) cabinet circuit short-circuit breaking capacity |
6kA |
|
External protection grade |
IP30 |
|
Touch protection classification |
Class I |
|
Rated insulation resistance |
0.9 |
Hot Tags: dual power distribution box, China dual power distribution box manufacturers, suppliers, factory, Reactive Power Compensation Device, Low Voltage Withdrawable Switchgear, Low Voltage Power Distribution Box, AC Metal Clad Withdrawable Switchgear, other transformer accessories, AC Low Voltage Power Distribution Cabinet